J. Appl. Poult. Res.
HOME HELP FEEDBACK SUBSCRIPTIONS ARCHIVE SEARCH TABLE OF CONTENTS
 QUICK SEARCH:   [advanced]


     


J APPL POULT RES 2008. 17:283-295. doi:10.3382/japr.2006-00055
© 2008 Poultry Science Association
This Article
Right arrow Full Text
Right arrow Full Text (PDF)
Right arrow Alert me when this article is cited
Right arrow Alert me if a correction is posted
Services
Right arrow Similar articles in this journal
Right arrow Similar articles in Web of Science
Right arrow Alert me to new issues of the journal
Right arrow Download to citation manager
Right arrow reprints & permissions
Citing Articles
Right arrow Citing Articles via Web of Science (1)
Right arrow Citing Articles via Google Scholar
Google Scholar
Right arrow Articles by Casey, K. D.
Right arrow Articles by Ford, M. J.
Right arrow Search for Related Content
PubMed
Right arrow Articles by Casey, K. D.
Right arrow Articles by Ford, M. J.

Field Reports

On-Farm Ventilation Fan Performance Evaluations and Implications

K. D. Casey*,1, R. S. Gates{dagger}, E. F. Wheeler{ddagger}, H. Xin§, Y. Liang#, A. J. Pescatore|| and M. J. Ford||

* Texas AgriLife Research, Texas A&M System, Amarillo, TX 79106;{dagger} Biosystems and Agricultural Engineering, University of Kentucky, Lexington 40546; {ddagger} Agricultural and Biological Engineering, Pennsylvania State University, University Park 16801; § Agricultural and Biosystems Engineering Department, Iowa State University, Ames 50011; # Biological and Agricultural Engineering, University of Arkansas, Fayetteville 72701; and || Animal and Food Sciences, University of Kentucky, Lexington 40546

1 Corresponding author: kdcasey{at}ag.tamu.edu

Fans are key components of mechanically ventilated poultry housing. When installed, the fan is often fitted with 1 or more accessories, including safety guards, shutters, and discharge cones. These first 2 accessories usually reduce the airflow and fan efficiency, whereas discharge cones improve airflow. Field performance of a fan is further impacted by accumulated dirt on the blades and shutters, mechanical wear, and degree of maintenance. Performance of all ventilation fans on 2 commercial broiler farms was determined during an air emission monitoring project. Each fan was tested using the Fan Assessment Numeration System at a range of static pressures typical of its regular operating range. The performance of otherwise identical fans was shown to vary by up to 24%. This variation in performance is attributed to accumulated dirt and corrosion, differences in the resistance to flow imposed by the shutters, and differences in motor and bearing wear due to run time and aging. A small reduction in fan speed from slipping or worn belts had a large effect on airflow generated by the 1,220-mm (48 in.) diameter fans. The power consumption of each fan was also measured as part of the evaluation process and revealed considerable variation among these fans.

Key Words: air movement • ventilation system maintenance • poultry housing • energy consumption • broiler • layer







HOME HELP FEEDBACK SUBSCRIPTIONS ARCHIVE SEARCH TABLE OF CONTENTS
Copyright © 2008 by the Poultry Science Association.